Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To View Another Inspection


Inspection #: 505739
Inspection Type: Final Electrical
Inspector: M.Green
Result: Partial
Comment: Am inspection please call Ryan @ 229-9527 when on site Requested by: Ryan Maidl 2299527 ryan@necak.com Conditional electrical final approved to run concurrently with fire final untill 3/14/2018. Conditional electrical final is for business set-up only and not for any opening to the public. Correct issues below and request electrical final inspection before opening for business. Inspected Gaming Area hanging ring signs. Ring signs have ETL listing marks and external disconnects. Inspected Gaming Area wall sign above "Win". Wall sign has ETL listing label but will require breaker lock due to no external disconnect. Item from 2/20/2018 partial final corrected: Vulcan ovens are CSA listed. Other item from 2/20/2018 partial final not corrected: LED lighting at "Mixmaster" reception desks and similar locations. Low voltage lighting info sent does not appear to show a listed low voltage lighting system, only UL recognized componants.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
2/20/2018TransferCorrect Below* Rooftop units in general.Cannot have conduit stub-ups within the 110.26 working clearances.
2/20/2018TransferCorrect Below* Arcade games (not on site).It is believed that many are not listed products. Any unlisted games will need field evaluation prior to use by the public.
2/20/2018CorrectedCorrect Below* Kitchen Vulcan stacked gas convection ovens do not appear to have a listing label.
2/20/2018TransferCorrect Below* Coat room" electrical panels240.24(D) generally prohibits OCPDs installed in close proximity to easily ignitable materials such as in clothes closets. Architectural DWGS show coat racking that appears to keep clothing away from panels. Will need to see finished arrangement to determine acceptability.
2/20/2018TransferCorrect Below* Mixmaster" reception desk. Other locations with similar low voltage lightingLow voltage transformer for reception desk built-in lighting not listed. Transformer not rated class 2. Tape strip LED lighting required to be supplied by class 2 transformer. Transformer 120V terminals not guarded against accidental contact and is not in an enclosure. Cannot have field installed cord and plug connection. Cord does not have strain relief. Low voltage lighting required to be listed as a system or be assembled from listed components. May be other issues.
2/20/2018TransferCorrect Below* RTU-3.Gas line violates 110.26 working clearances.
2/20/2018TransferCorrect Below* Rooftop walk-in cooler / freezer condensor.Gas line violates working clearances.
2/20/2018TransferCorrect Below* Rooftop ice machine condensors.Need disconnects within sight.
2/20/2018TransferCorrect Below* Rooftop RTU-11, RTU-12.Ductwork under electrical compartment violates 110.26 working clearances. Electrical compartment door will not open 90 degrees. Units are 480V.
2/14/2018CorrectedCorrect Below* Function room.(1) EM light not functioning.
2/14/2018CorrectedCorrect Below* Back of house.Hallway: No EM or EM light not functioning and (1) exit sign not on. Bathroom: EM light not functioning.
2/14/2018CorrectedCorrect Below* Back part of kitchen.Either does not have an emergency light or EM light not functioning.
2/14/2018TransferCorrect Below* Restaurant.Normal business hours lighting is from 120V panel(s). Emergency lighting is by means of 277V strip lights with battery back-up. The 277V strip lights are not normal business hours lighting; a controller / timer only energizes strip lights for after hours cleaning. This design does not meet the requirements of 700.12.
2/13/2018TransferCorrect Below* Gaming area.Ambient lighting during business hours is to be provided by 120V arcade games. Emergency lighting designed for the area is by means of 277V strip lights with battery back-up. The 277V strip lights with EM battery back-up are not used for normal lighting during business hours. Timer / controller system only energizes lights after hours for cleaning staff. Concerns are as follows: 1. 700.12 requires the EM lights to be on the same circuit as normal lighting in the area served. These lights are not normal lighting. An exception permits a dedicated circuit for EM lights if fed from the same panel feeding normal lighting. This design does not meet either requirement. 2. FA system will deenergize games on alarm. Gaming area EM lights will not come on leaving the area in the dark.
ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter