Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To View Another Inspection


Inspection #: 505621
Inspection Type: Final Electrical
Inspector: M.Green
Result: Correction
Comment: Am inspection please call Ryan @ 229-9527 when on site Requested by: Ryan Maidl 2299527 ryan@necak.com Progress electrical final for kitchen and dry storage receptacles test and equipment listings. Also, corrected EM lighting issues from inspection number 499404 in kitchen, back of house, function room. Other items from inspection numbers 499404 and 499024 remain unresolved. Not all outstanding corrections from previous finals are carrying forward to this inspection.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
2/14/2018TransferCorrect Below* KitchenVulcan stacked gas convection ovens do not appear to have a listing label.
2/14/2018TransferCorrect Below* Kitchen 120V, single receptacles.210.8(B) requires all `125V, 1-phase, 15 and 20A receptacles installed in kitchens to be GFCI protected.
2/13/2018TransferCorrect Below* Panels for gaming area.Many dedicated circuits to power poles. Impossible to detail on a panel schedules. Post electrical floor plans to show location of circuits.
2/13/2018TransferCorrect Below* Coat room" electrical panelsEngineer needs to show a code path to allow panels in a walk-in closet. See 240.24(D). OCPD not to be located in vicinity of easily ignitable material such as clothes closets.
2/13/2018TransferCorrect Below* Mixmaster" reception desk at top of stairsLow voltage transformer for reception desk built-in lighting is not listed. Transformer is not rated class 2. Transformer 120V terminals are not guarded against contact. Transformer is not in an enclosure. Low voltage transformers generally not permitted for use with a field installed cord and plug connection without strain relief. Low voltage lighting required to be listed as a system or assembled from listed parts per 411.4. May be other issues.
ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter