Inspection #: 505120
Inspection Type: Plumbing Rough
Inspector: E.Huckaba
Result: Partial
Comment: Mobile Home Setup- APPROVED. NOTES: MOA HANDOUT REGARDING MOBILE HOME STRAPPING HAS BEEN SIGNED, DATED 2-13-18 AND POSTED NEXT TO PERMIT. GREEN TAG ISSUED, GAS= FAF, RANGE and HWH(NOT FLUED).

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
2/8/2018CorrectedPlumbRgh14CommentsSee Inspectors CommentsDwv piping under the trailer.Per 2012 UPC section 701.1 and 706.2 improper use of fittings. 2-way clean out is not an approved fitting to pipe toilet waste. Please use proper waste and vent fittings.
2/8/2018CorrectedPlumbRgh4ABS/PVC SupportABS/PVC horizontal piping shall be supported every 4 feet horizontally- UPC Table 313.1Dwv piping under the trailer.Per 2012 UPC section 313.1 ABS piping must be supported every 4ft.
2/8/2018CorrectedPlumbRgh12Piping SupportPiping is not properly supported- UPC Section 313.0, including Table 313.1Water piping ( pex )Per 2012 UPC section 313.1 pex piping must be supported every 32''