| Date | Status | Code | Description | Ref | Location | Comments |
| 2/8/2018 | Transfer | PlumbRgh14 | Comments | See Inspectors Comments | Dwv piping under the trailer. | Per 2012 UPC section 701.1 and 706.2 improper use of fittings. 2-way clean out is not an approved fitting to pipe toilet waste. Please use proper waste and vent fittings. |
| 2/8/2018 | Transfer | PlumbRgh4 | ABS/PVC Support | ABS/PVC horizontal piping shall be supported every 4 feet horizontally- UPC Table 313.1 | Dwv piping under the trailer. | Per 2012 UPC section 313.1 ABS piping must be supported every 4ft. |
| 2/8/2018 | Transfer | PlumbRgh12 | Piping Support | Piping is not properly supported- UPC Section 313.0, including Table 313.1 | Water piping ( pex ) | Per 2012 UPC section 313.1 pex piping must be supported every 32'' |
| 2/7/2018 | Transfer | PlumbRgh14 | Comments | See Inspectors Comments | UNDERSIDE OF TRAILER | HOLD DOWNS/ STRAPS NOT INSTALLED AT THIS TIME. |
| 2/7/2018 | Corrected | GasPipeRgh | Medium Pressure Test | Medium pressure gas piping requires a 60# test- UPC local amendment 23.25.1210.5.2 | UNDERGROUND GAS LINE FROM METER TO TRAILER | GAS LINE NOT ON TEST. 60# TEST NEEDED FOR GREEN TAG. |