Inspection #: 504251
Inspection Type: Fire Sprinkler Rough-In
Inspector: B.Meinhardt
Result: Correction
Comment: Fire Sprinkler Rough-In, Contact is Andrew Anderson 727-4163, 400 devices. Thank you, Requested by: Wendee Gilchrist 907-336-5000 wgilchrist@gmwfire.com

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
2/1/2018TransferFireSprnkRoughOtherFire Sprinkler Rough Partial ApprovalFire Sprinkler Rough Partial Approval.   List area(s) approved Rough in and hydro for the kitchen and back of house approved. 2/5/2017 (1) North end add 4 head around the elevator area (a) front of elevator (b) north east corner (c) by storage room northwest corner (d) by elevator room to the east (2) outside fun room 1 and 2 ceiling heads head spaced less than 6 feet apart (3) need to add to 2 lines in the south west seating area, sprinkler line is 9 feet of the wall and other lines is blocked by solid beam and other heads are 10 feet away (4) multiple heads are still covered in tape in the black ceilings and in bathroom storage room (5) bathroom heads are loaded with sheet rock mud or paint and need to be replaced.