Date | Status | Code | Description | Ref | Location | Comments |
2/16/2018 | | firesprinkl13 | CCO Approved | CCO approved for fire sprinkler system | | Fire sprinkler approved for CCO until April 1, 2018 |
2/16/2018 | | firesprinkl9 | Add heads | Provide additional heads as directed | | Add sprinkler head to top of garbage compactor chute |
2/16/2018 | | FireSprinklerFinalOther | Please correct the following | Please correct the following: | | Main drain test was 45 PSI which is lower than the hydraulic calculation demand for the fire sprinkler system. Have the designer check the design. |