Inspection #: 504102
Inspection Type: Fire Sprinkler Final
Inspector: B.Meinhardt
Result: Partial
Comment: 557 Devices Contact: Andrew Anderson 727-4163 Dave and Buster T.I. Requested by: Billy Bayer 229-5571 billybayer@gmwfire.com Requested by: Billy Bayer 229-5571 billybayer@gmwfire.com

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
2/16/2018 firesprinkl13CCO ApprovedCCO approved for fire sprinkler system Fire sprinkler approved for CCO until April 1, 2018
2/16/2018 firesprinkl9Add headsProvide additional heads as directed Add sprinkler head to top of garbage compactor chute
2/16/2018 FireSprinklerFinalOtherPlease correct the followingPlease correct the following: Main drain test was 45 PSI which is lower than the hydraulic calculation demand for the fire sprinkler system. Have the designer check the design.