Inspection #: 504057
Inspection Type: Final Fire Inspection
Inspector: B.Meinhardt
Result: CondAppr
Comment: Please contact Mike Swiantek at 727-1496 prior to heading to jobsite. Requested by: Mike Swiantek 727-1496 nate@mcnconstruction.com

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
2/16/2018TransferFireOtherOtherCorrection(s) #1Please correct the following item(s): Install signs on the following rooms: "Fire Sprinkler Room", "Fire Alarm Room" CO2 Hazard on door of room with CO2 tank.
2/16/2018TransferFire 6Emergency lights<span>Additional Emergency lights required. </span> Final evaluation of the exit signs and emergncy lighting levels will be verified after the games are installed
2/16/2018TransferFire 13Correction(s) #1Please correct the following: Complete fire extinguisher installation in the gaming area after the games are installed. Install fire extinguishers signs as required were the fire extignuishers are obstructed from view.
2/16/2018TransferFire 13Correction(s) #1Please correct the following: Complete 2nd floor doors to the mall and 1st floor doors to the mall.
2/16/2018TransferFire 9Knox keyFire Dept approved Knox Box required at Front Main Entry with keys to building for emergency responders.  Install Keys in the KNOX BOX call 267-4950 to schedule a fire crew to install
2/16/2018TransferFireOtherOtherCorrection(s) #1Please correct the following item(s): Complete kitchen fire systems, fire alarm and fire sprinkler systems
2/16/2018TransferFire 6Emergency lights<span>Additional Emergency lights required. </span> Emergency lighting operation needs to be resolved on when the fire alarm system operates or a power outage and the games shut down that provide ambiant lighting. Emergency lighting needs to stay operational until the games provide the code requied minimum lighting level of 1 foot candle average on the walking/egress surface.
2/16/2018TransferFire 2CCO approvalFire Final approved for CCO CCO approved till March 14, 2018 for installation of Fixtures and Furniture, Electronics, Employees and Contractors. NO PUBLIC ALLOWED, NO USE of the KITCHEN HOOD and APPLIANCES.