Inspection #: 503384
Inspection Type: Fire Sprinkler Rough-In
Inspector: M.Warren
Result: Correction
Comment: 557 Devices Contact: Andrew Anderson 727-4163 Hydro-Roughin Dave and Buster TI Requested by: Billy Bayer 336-5000 billybayer@gmwfire.com

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
1/31/2018TransferFireSprnkRoughOtherFire Sprinkler Rough Partial ApprovalFire Sprinkler Rough Partial Approval.   List area(s) approved Partial rough in inspection, Drop metro flex to brace correctly at fun1/kitchen. Brace metroo just south of fun room 2. brace longitutal at the north side of metro in the rtu room. expose bracing at the bar area. lateral brace at grid 4 and 13/A. Brace 4 inch at 13 line per plan. kitchen area needs branch line restraints and coverage behind the hood in the interstitial space.