Inspection #: 502540
Inspection Type: Ceiling Rough Electrical
Inspector: E.Widman
Result: Partial
Comment: Electrical rough above accessible ceiling approved.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
1/16/2018CorrectedEC1Correct Below lower level Verify new emergency lighting is not on multiwire branch ckt. Reference local amendment 23.30.700.19. Maximum of 6 permitted to be replaced and remain on multiwire branch.
1/16/2018CorrectedEC1Correct Below Various locations at lower level ceiling. Suspended ceiling removed and replaced. Properly support conduit and cables per NEC.
1/16/2018CorrectedEC1Correct Below Identify ceiling wires installed for electrical support.  
1/16/2018CorrectedEC1Correct Below Provide MOA stamped reviewed drawings for reinspection.  