| Date | Status | Code | Description | Ref | Location | Comments |
| 2/27/2018 | | ACTC | See Inspector comments | Inspector comments | | Elevator lobby walls to be 1 hour rated, complete framing, 5/8 type X and firestopping at these walls in basement and label walls per IBC 703.7 Marking and identification. Fire walls, fire barriers,
fire partitions, smoke barriers and smoke partitions or any
other wall required to have protected openings or penetrations
shall be effectively and permanently identified with
signs or stenciling. Such identification shall:
1. Be located in accessible concealed floor, floor-ceiling
or attic spaces;
2. Be located within 15 feet (4572 mm ) of the end of each
wall and at intervals not exceeding 30 feet (9144 mm)
measured horizontally along the wall or partition; and
3. Include lettering not less than 3 inches (76 mm ) in
height with a minimum 3/8 inch (9.5 mm) stroke in a
contrasting color incorporating the suggested wording.
“FIRE AND/OR SMOKE BARRIER—PROTECT
ALL OPENINGS” or other wording. |
| 1/16/2018 | | ACTC | See Inspector comments | Inspector comments | | Where required provide identification of rated walls above cielings |
| 1/16/2018 | Corrected | ACTC | See Inspector comments | Inspector comments | | Provide wires to support Tees over 8 inches in length. |