Inspection #: 502518
Inspection Type: Ceiling / Act
Inspector: D.Hickel
Result: Approved
Comment: ACT grid in basement approved

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
2/27/2018 ACTCSee Inspector commentsInspector comments Elevator lobby walls to be 1 hour rated, complete framing, 5/8 type X and firestopping at these walls in basement and label walls per IBC 703.7 Marking and identification. Fire walls, fire barriers, fire partitions, smoke barriers and smoke partitions or any other wall required to have protected openings or penetrations shall be effectively and permanently identified with signs or stenciling. Such identification shall: 1. Be located in accessible concealed floor, floor-ceiling or attic spaces; 2. Be located within 15 feet (4572 mm ) of the end of each wall and at intervals not exceeding 30 feet (9144 mm) measured horizontally along the wall or partition; and 3. Include lettering not less than 3 inches (76 mm ) in height with a minimum 3/8 inch (9.5 mm) stroke in a contrasting color incorporating the suggested wording. “FIRE AND/OR SMOKE BARRIER—PROTECT ALL OPENINGS” or other wording.
1/16/2018 ACTCSee Inspector commentsInspector comments Where required provide identification of rated walls above cielings
1/16/2018CorrectedACTCSee Inspector commentsInspector comments Provide wires to support Tees over 8 inches in length.