Date | Status | Code | Description | Ref | Location | Comments |
2/13/2018 | Transfer | Correct Below | * | | Panels for gaming area. | Many dedicated circuits to power poles. Impossible to detail on a panel schedules. Post electrical floor plans to show location of circuits. |
2/13/2018 | Transfer | Correct Below | * | | Coat room" electrical panels | Engineer needs to show a code path to allow panels in a walk-in closet. See 240.24(D). OCPD not to be located in vicinity of easily ignitable material such as clothes closets. |
2/13/2018 | Transfer | Correct Below | * | | Mixmaster" reception desk at top of stairs | Low voltage transformer for reception desk built-in lighting is not listed. Transformer is not rated class 2. Transformer 120V terminals are not guarded against contact. Transformer is not in an enclosure. Low voltage transformers generally not permitted for use with a field installed cord and plug connection without strain relief. Low voltage lighting required to be listed as a system or assembled from listed parts per 411.4. May be other issues. |