Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To View Another Inspection


Inspection #: 499024
Inspection Type: Final Electrical
Inspector: M.Green
Result: Correction
Comment: Pm inspection, Please call Ryan when on site 229-9527 Requested by: Ryan maidl 229-9527 ryan@necak.com Gaming area plug test progress electrical final.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
2/13/2018TransferCorrect Below* Panels for gaming area.Many dedicated circuits to power poles. Impossible to detail on a panel schedules. Post electrical floor plans to show location of circuits.
2/13/2018TransferCorrect Below* Coat room" electrical panelsEngineer needs to show a code path to allow panels in a walk-in closet. See 240.24(D). OCPD not to be located in vicinity of easily ignitable material such as clothes closets.
2/13/2018TransferCorrect Below* Mixmaster" reception desk at top of stairsLow voltage transformer for reception desk built-in lighting is not listed. Transformer is not rated class 2. Transformer 120V terminals are not guarded against contact. Transformer is not in an enclosure. Low voltage transformers generally not permitted for use with a field installed cord and plug connection without strain relief. Low voltage lighting required to be listed as a system or assembled from listed parts per 411.4. May be other issues.
ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter