Inspection #: 497102
Inspection Type: Wall Rough Electrical
Inspector: M.Green
Result: Correction
Comment: Ryan Maidl, 229-9527 Requested by: Linda Tegeler 907/357-5222 lindat@necak.com Function rooms walls and ceilings. "Gang bathrooms" and adjacent corridor walls and ceilings. Electrical rough approved except for correction items below.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
12/5/2017 Correct rough-in item below* Automatic toilet flushers.Class 2 transformers are not listed - only UR marked.
12/5/2017 Correct rough-in item below* Restrooms automatic toilet flushers.Calss 1 wiring, Class 2 transformer, and Class 2 secondary wiring cannot all be in the same 4sq box. No reliable separation between Class 1 and Class 2.