Date | Status | Code | Description | Ref | Location | Comments |
11/22/2017 | Corrected | Correct Below | * | | Gutters above panels. | May be issues concerning number of conductors (n0 m0re tan 30 in any cross sectional area) |
11/22/2017 | Corrected | Correct Below | * | | Inverter feeding emergency lighting. | Feed to inverter needs to originate from same panel as normal lighting. |
11/22/2017 | Corrected | Correct Below | * | | Inverter serving corridor emergency lighting. | Post a map or some way to determine emergency lights served. |
11/22/2017 | Corrected | Correct Below | * | | Panels feeding remodel area. | Update circuit designations of circuits worked on as part of this project. |