Inspection #: 496495
Inspection Type: Fire Alarm Final
Inspector: B.Meinhardt
Result: Correction
Comment: CRAIG 907-841-2045 9:00 AM

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
5/5/2018Transferfirealarm13Please correct the followingPlease correct the following: All fire alarm ititating devices still need to be tested plus 10% of the existing. Problem with the alarm after alarm silenced and reset, the second alarm would not sound the horn strobes in the IMC/libary area
5/5/2018TransferFireWalarmFinalOtherFire Alarm Final OtherPlease correct the following: Submit change order to the fire alarm plans for approval. Ordinally SLC was from West panel and now it is on the ROMING panel
5/5/2018Transferfirealarm13Please correct the followingPlease correct the following: Hall between libary and west high strobes is out of sync by double doors per 2010 NFPA 72 section 18.5.4.3.2 (3) & (4)
5/5/2018Transferfirealarm1Provide plansProvide approved plans on site for inspection. Provide approved plans at next test
5/5/2018Transferfirealarm2Install cert <p class="MsoNormal"><font face="Times New Roman">Provide Installation Certification and test report.</font></p>  Provide fire alarm installers cert
5/5/2018Transferfirealarm6FACP mapFloor plan/map required at main entry door showing location of FACP. Provide updated Fire Alarm Map