Inspection #: 496440
Inspection Type: Final Electrical
Inspector: M.Green
Result: Partial
Comment: please call 30min before inspection Requested by: Scott Cormier 9073518810 talonelectric1@gmail.com New north entry facade improvements.Complete electrical final was approved on 2/2/2018 in error. Conditional electrical final approved until 3/2/2018 to resolve the following notes: 1. LED pedestrian crossing signs need field evaluation. 2. Verify that the service is labelled with available fault current calculations and that this service has a label that shows location of other services on the building.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
11/21/2017TransferCorrect Below* Ped xing signs Do not use until listing can be established or until field evaluated.
11/21/2017TransferCorrect Below* PlansNeeds engineered 1-line dwg.
11/21/2017TransferCorrect Below* Panel N.Needs permanent panel schedule. Needs "fed from" label.
11/21/2017TransferCorrect Below* Exterior planter receptacles, etc.Runs not pulled.
11/21/2017TransferCorrect Below* Light box above canopyComplete wiring.
11/21/2017TransferCorrect Below* Under canopy.(2) LED strip lights on order.