| Date | Status | Code | Description | Ref | Location | Comments |
| 11/14/2017 | Corrected | INTFRAMEB | Interior framing correction | Complete the following corrections | | Preliminary walk through with C. Mosley - Cornerstone G.C. Several areas need to be addressed by Architect and Owner. Existing curbs at the egress doors are not allowed in the boiler/mechanical and electrical rooms. If door IMC-5-2 is eliminated the room will exceed 500 sq. ft. and require two means of egress (IBC 1015.3). Fire pump room requires 1 hour fire barrier and individual protection of structural members for 1 hour (IBC 913.2.1 and 704). Owner and Architect to address these issues as well as any additional issues i.e. fire/smoke dampers, rated wall assemblies, etc. More items may be encountered as inspections progress. |