Inspection #: 494467
Inspection Type: Framing / Int.
Inspector: D.Hickel
Result: Correction
Comment:

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
11/14/2017TransferINTFRAMEBInterior framing correctionComplete the following corrections Preliminary walk through with C. Moseley - Cornerstone G.C. Several areas need to be addressed by Architect and Owner. Existing curbs at the egress doors are not allowed in the boiler/mechanical and electrical rooms. If door IMC-5-2 is eliminated the room will exceed 500 sq. ft. and require two means of egress (IBC 1015.3). Fire pump room requires 1 hour fire barrier and individual protection of structural members for 1 hour (IBC 913.2.1 and 704). Owner and Architect to address these issues as well as any additional issues i.e. fire/smoke dampers, rated wall assemblies, etc. More items may be encountered as inspections progress.