Inspection #: 493996
Inspection Type: Final Electrical
Inspector: M.Green
Result: Partial
Comment: CCO per previous inspection Requested by: Cody Tims 907-227-0050 Ctims@megawattelectric.com Partial, conditional electrical final approved for: Corridor portion of project from new north facade entranceto cetral electrical room. Correct the following items and call for reinspection by 12/15/2017. Inspection actually performed on 11/21/2017 while performing scheduled inspection for E17-1574.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
11/22/2017CorrectedCorrect Below* Gutters above panels.May be issues concerning number of conductors (n0 m0re tan 30 in any cross sectional area)
11/22/2017CorrectedCorrect Below* Inverter feeding emergency lighting.Feed to inverter needs to originate from same panel as normal lighting.
11/22/2017CorrectedCorrect Below* Inverter serving corridor emergency lighting.Post a map or some way to determine emergency lights served.
11/22/2017CorrectedCorrect Below* Panels feeding remodel area.Update circuit designations of circuits worked on as part of this project.