Inspection #: 491279
Inspection Type: Service
Inspector: O.Burbridge
Result: Correction
Comment: service at foam building approved tag 33464

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
11/2/2017TransferCorrect service item below* MCC building servicebond service entrance conduits with #3/0 cu
11/2/2017TransferCorrect service item below* both servicesconduit for ground wire must be bonded at both sides or use PVC
11/2/2017TransferCorrect service item below* MCC buildinglugs must be listed for fine strand wire or use compression termination pins
11/2/2017TransferCorrect service item below* both services placards required for available fault current/date calculated
11/2/2017TransferCorrect service item below* foam buildingexterior main disconnect/ground rods required