Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To View Another Inspection


Inspection #: 484362
Inspection Type: Fire Alarm Final
Inspector: B.Meinhardt
Result: Partial
Comment: All audible testing must be completed by 10 am. Partial test of system to include all input devices and output functions. Final audible testing to be completed after all games and furniture has been installed. Intelligibility and DB testing not performed for this inspection. Requested by: Michael Johnson 907 231-3050 michael.johnson4@honeywell.com

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
2/16/2018 FireWalarmFinalOtherFire Alarm Final OtherPlease correct the following: Not all duct detectors are reporting and some decriptions do not match.
2/16/2018 FireWalarmFinalOtherFire Alarm Final OtherPlease correct the following: Kitchen hood fire system alarm wiring is not to code. fire alarm wiring is not connected to the alarm micro switch (with screw down terminals). There is no end of line resistor located at the microswitch for supervision of the wiring.
2/16/2018TransferFireWalarmFinalOtherFire Alarm Final OtherPlease correct the following: Need to complete the following testing: Audiblity/Intelligblity testing, Game and TV shut downs, ansul hoods and complete outstanding items.
2/16/2018TransferFireWalarmFinalOtherFire Alarm Final OtherPlease correct the following: Lable fire alarm devices Pull Stations and Smoke Detectors on Node 1 serving the south stiars as Dave and Busters
2/16/2018Transferfirealarm8Batt test failed24 hour battery test failed. Recall after replacement Need to complete battery test once all items are installed
2/16/2018Transferfirealarm6FACP mapFloor plan/map required at main entry door showing location of FACP. Provide Fire Alarm map at each annuciator
2/16/2018Transferfirealarm5FACP signSign required at room door where FACP located. Install sign on door to fire alarm panel "Fire Alarm Panel"
2/16/2018Transferfirealarm4MonitoringVerify monitoring by an outside agency Complete final monitoring change over, currently on temp monitoring through mall.
2/16/2018Transferfirealarm3Decibel reportProvide Decibel Level Report. Need to witness intelligiblity testing and dB testing after the games and TVs are installed
2/16/2018Transferfirealarm2Install cert <p class="MsoNormal"><font face="Times New Roman">Provide Installation Certification and test report.</font></p>  Provide installers cert at final testing after games are installed
2/16/2018TransferFireOtherOtherCorrection(s) #1Please correct the following item(s): add one strobes to the east of the gaming room stairs that is blocked by ductwork
2/16/2018Transferfirealarm11Fire Alarm approved CCOFire Alarm approved for CCO Fire Alarm approved for CCO till March 14, 2018. Fire Alarm is functional for furniture and fixture installation, contractor and employee setup of the facility. NO PUBLIC OCCUPANCY ALLOWED.
ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter      RSS