Inspection #: 483074
Inspection Type: Gas Piping
Inspector: K.Hanson
Result: Partial
Comment: Partial Gas - Approved Gas rough & tests approved for rooftop main & branches within grid lines M-R & 11-14, serving RTUs 7-9 & future Dave & Buster's outlets. Temp tag issued, RTU-7 set. NOTE 1: As per 2012 IFGC 410.2 paragraphs 5 & 6, test tees required. NOTE 2: Gas connection to RTUs to be inspected next visit.