Inspection #: 482619
Inspection Type: Final Electrical
Inspector: E.Widman
Result: Correction
Comment: Corrections. Bond Gas piping and water piping sytems into building disconnect. GEC must connect to building disconnect grounding. Label disconnect with feed. Label feeder overcurrent protection for structures.