Inspection #: 482076
Inspection Type: Electrical Rough
Inspector:
Result:
Comment:

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
10/6/2017 01See inspection comments Any other exterior receptacles including under trailer.Show at next inspection that these are GFCI protected. If replacing receptacles, any replaced receptacles will need to be tamper resistant and weather resistant types.
10/6/2017 01See inspection comments Under mobile home.Make sure that ground wire to gas and water lines bonds to metal trailer frame.
10/6/2017 01See inspection comments Metal feeder j-box under trailer.Bond feeder ground wire to box. Unused opening needs knock-out seal.
10/6/2017 01See inspection comments Post mounted disconnect.Bond ground and neutral bars together with #6 copper wire.
10/6/2017 01See inspection comments Underground feeder conduit at post mounted disconnect.Liquidtight non-metallic flex needs to connect to the PVC conduit with proper fittings; not just stub into the conduit.
10/6/2017 01See inspection comments Underground feeder.Depth is not 18 inches at the end by the trailer. (Depth is OK along most of the trench.) Dig trench deeper and leave open for next inspection.