| Date | Status | Code | Description | Ref | Location | Comments |
| 10/6/2017 | Transfer | 01 | See inspection comments | | Any other exterior receptacles including under trailer. | Show at next inspection that these are GFCI protected. If replacing receptacles, any replaced receptacles will need to be tamper resistant and weather resistant types. |
| 10/6/2017 | Transfer | 01 | See inspection comments | | Under mobile home. | Make sure that ground wire to gas and water lines bonds to metal trailer frame. |
| 10/6/2017 | Transfer | 01 | See inspection comments | | Metal feeder j-box under trailer. | Bond feeder ground wire to box. Unused opening needs knock-out seal. |
| 10/6/2017 | Transfer | 01 | See inspection comments | | Post mounted disconnect. | Bond ground and neutral bars together with #6 copper wire. |
| 10/6/2017 | Transfer | 01 | See inspection comments | | Underground feeder conduit at post mounted disconnect. | Liquidtight non-metallic flex needs to connect to the PVC conduit with proper fittings; not just stub into the conduit. |
| 10/6/2017 | Transfer | 01 | See inspection comments | | Underground feeder. | Depth is not 18 inches at the end by the trailer. (Depth is OK along most of the trench.) Dig trench deeper and leave open for next inspection. |