Inspection #: 480036
Inspection Type: Electrical Rough
Inspector: O.Burbridge
Result: Correction
Comment: electrical ug to inbound protal and light pole approved

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
10/6/2017Transfer01See inspection comments  workspace req at rtu's
10/6/2017Transfer01See inspection comments  add gec for ups
9/29/2017Corrected01See inspection comments Feed to bypass switch in server room. #3 cu ran to bypass. Plans call for #2 cu. Equipment and ckts rated 100 amp or less must use conductors referenced in 110.14 (C) (1), and use next higher standard ampere rating. Reference 240.4 (B) and 240.6 (A).
9/29/2017Transfer01See inspection comments Securely fasten flexible conduit at UPS.  