Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To View Another Inspection


Inspection #: 471061
Inspection Type: Electrical Rough
Inspector: M.Green
Result: Correction
Comment: May call Mike at 317-6980 if questions. Strongly suggest using electrical contractor to make corrections.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
9/20/2017Transfer01See inspection comments Under mobile home.The #6 copper wire that connects the water line and gas line to the electrical panel also needs to bond to the trailer frame. Be prepared to show this connection at the next inspection.
9/20/2017Transfer01See inspection comments Under mobile home.Support any MC cable or romex up off of the ground to the trailer frame.
9/20/2017Transfer01See inspection comments Any other exterior receptacles including under the trailer.Show at next inspection that these (if any) are GFCI protected. Any receptacles that need to be replaced will have to be tamper resistant / weather resistant type (marked with both TR and WR.
9/20/2017Transfer01See inspection comments Headbolt heater receptacle at front exterior of trailer.Receptacle needs to be weather resistant type (in addition to being tamper resistant type).
9/20/2017Transfer01See inspection comments Metal feeder j-box under trailer.Feeder ground wire needs to be bonded to this j-box.
9/20/2017Transfer01See inspection comments Underground feeder from post mounted disconnect at trailer space to trailer.Feeder burried without inspection. Will need to verify 24 inch depth if conductors are direct burried or 18 inch depth if in raceway.
9/20/2017Transfer01See inspection comments Post mounted disconnect at trailer.Liquidtight non-metallic flex conduits run from disconnect to grade level. Correct the following: 1. Use connectors for liquidtight non-metallic flex,; not EMT or steel flex connectors. 2. Conduit cannot enter disconnect enclosure through over sized hole. 3. Liquidtight flex needs to connect to the larger PVC underground conduit: not just stub into it.
9/20/2017Transfer01See inspection comments Post mounted disconnect at trailer space.Do not use (2) 100A circuit breakers to protect (1) feeder into the trailer. Both hot wires need to terminate on (1) circuit breaker.
9/20/2017Transfer01See inspection comments Post mounted disconnect at trailer space.Neutral and ground bars need to be bonded together with #6 copper wire.
9/20/2017Transfer01See inspection comments Post mounted disconnect at trailer space.1. Needs (2) ground rods driven 6 ft appart (only one installed).
ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter      RSS