Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To View Another Inspection


Inspection #: 470257
Inspection Type: Final Electrical
Inspector: M.Green
Result: Correction
Comment: Store does not open until 10am. Requesting to clear the conditional final and re-inspect for corrections. Roogtop AC unit disconnect was replaced with a NEMA3R 30A non-fused disconnect and labeled with engraved phenolic as requested. Breaker size changed to a 3pole 20A QO bolt on.New prints submitted for emergency lighting. Change order submitted and approved. Store lighting changed in unison. Source of power labeled inside panel. Key for main breaker room is up to GameStop and the Dimond center :)Requested by: Brandon 907-414-0908 ITEMS UNDER DIRECT CONTROL OF ELECTRICAL CONTRACTOR HAVE BEEN RESOLVED. (2) ITEMS NOT UNDER THE DIRECT CONTROL OF THE ELECTRICAL CONTRACTOR HAVE NOT BEEN RESOLVED.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
8/22/2017TransferCorrect Below* Access to Game Stop feeder breaker.Tennant required to have a key to th locked electrical room housing the feeder breaker. Mall management to provide letter stating that tennant will have posession of the key. Personnel on site could not demonstrate access nor produce a letter stating that the tennant will have the key .
8/22/2017TransferCorrect Below* Engineering / plans.Engineer needs to verify correct source of supply for Game Stop tennant panel. Label panel as to source of supply. Label Game Stop feeder breaker with correct space / suite number. no drawings on site. If 1-line drawings are different from actual installation, engineer needs to change drawing and submit change to MOA plan review for approval. Changed drawings with moa plan approval stamp must be on site and available to the inspector at the next site visit.
8/22/2017CorrectedCorrect Below* Rooftop condenser unit.1-line dwg shows a new, 30A, non-fused disconnect, protected by a 30A breaker. Label disconnect as to source of supply and space served. Labelling must be suitable forthe environment. (Existing fused disc. does not have working clearances, cannot determine fuse sizes. EGC not bonded to enclosure, 40A breaker supplies unit.)
8/22/2017CorrectedCorrect Below* Sales floor.(2) EM battery back-up troffers not functioning in emergency mode. EM battery packs on order. (2) other EM troffers are functioning. AFD may not approve a conditional final with (2) of (4) EM lights functioning.
ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter