Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To View Another Inspection


Inspection #: 469979
Inspection Type: Final Electrical
Inspector: M.Green
Result: Partial
Comment: Game Stop TI electrical final inspection. Conditional electrical final approved until 9/22/2017 to resolve corrections items.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
8/22/2017TransferCorrect Below* Access to Game Stop feeder breaker.Tennant required to have a key to th locked electrical room housing the feeder breaker. Mall management to provide letter stating that tennant will have posession of the key.
8/22/2017TransferCorrect Below* Engineering / plans.Engineer needs to verify correct source of supply for Game Stop tennant panel. Label panel as to source of supply. Label Game Stop feeder breaker with correct space / suite number.
8/22/2017TransferCorrect Below* Rooftop condenser unit.1-line dwg shows a new, 30A, non-fused disconnect, protected by a 30A breaker. Label disconnect as to source of supply and space served. Labelling must be suitable forthe environment. (Existing fused disc. does not have working clearances, cannot determine fuse sizes. EGC not bonded to enclosure, 40A breaker supplies unit.)
8/22/2017TransferCorrect Below* Sales floor.(2) EM battery back-up troffers not functioning in emergency mode. EM battery packs on order. (2) other EM troffers are functioning. AFD may not approve a conditional final with (2) of (4) EM lights functioning.
ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter