Inspection #: 469599
Inspection Type: Fire Alarm Final
Inspector: M.Warren
Result: Partial
Comment: Hello. We are requesting a Fire Alarm inspection for F17-1183, 5th Ave Mall, 3rd Floor Common Space, on Tuesday, November 14th, in the AM. Kathy Tranum will be the tech attending. Please call her with an ETA, 907-223-4367. Please aim to have all audio testing completed by 9:30am. The earlier the better. Thank you. Requested by: Joshua Olds 907-317-1633 jolds@atsalaska.com

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
11/15/2017Transferfirealarm13Please correct the followingPlease correct the following: Repair ground fault to panel at the roof smoke control.
11/15/2017Transferfirealarm13Please correct the followingPlease correct the following: Install smoke zone map at main fire alarm panel.
11/15/2017Transferfirealarm13Please correct the followingPlease correct the following: Install an additional pull at the north stair #5.
11/15/2017Transferfirealarm13Please correct the followingPlease correct the following: Beam detectors are on supervisory and need to be on alarm.
11/15/2017Transferfirealarm13Please correct the followingPlease correct the following: Remove old fire fighter phones.
11/15/2017Transferfirealarm13Please correct the followingPlease correct the following: Fix hinge on wond door to Nordstroms. It hangs up the fire door to not operate properly.
11/15/2017Transferfirealarm13Please correct the followingPlease correct the following: Remove old horm/strobe at the stairs #3 and #6.
11/15/2017Transferfirealarm13Please correct the followingPlease correct the following: Remove non operational pull at 3rd floor sky bridge to Nordstroms.
11/15/2017Transferfirealarm11Fire Alarm approved CCOFire Alarm approved for CCO This inspection is for the third floor common area detection and notification. Note to the mall manegement that a CCO for the alarm will not be given until all suite addressing is the same as the fire alarm description. This has been discussed several times with the mall that it will be required.