| Date | Status | Code | Description | Ref | Location | Comments |
| 11/15/2017 | Transfer | firealarm13 | Please correct the following | Please correct the following: | | Repair ground fault to panel at the roof smoke control. |
| 11/15/2017 | Transfer | firealarm13 | Please correct the following | Please correct the following: | | Install smoke zone map at main fire alarm panel. |
| 11/15/2017 | Transfer | firealarm13 | Please correct the following | Please correct the following: | | Install an additional pull at the north stair #5. |
| 11/15/2017 | Transfer | firealarm13 | Please correct the following | Please correct the following: | | Beam detectors are on supervisory and need to be on alarm. |
| 11/15/2017 | Transfer | firealarm13 | Please correct the following | Please correct the following: | | Remove old fire fighter phones. |
| 11/15/2017 | Transfer | firealarm13 | Please correct the following | Please correct the following: | | Fix hinge on wond door to Nordstroms. It hangs up the fire door to not operate properly. |
| 11/15/2017 | Transfer | firealarm13 | Please correct the following | Please correct the following: | | Remove old horm/strobe at the stairs #3 and #6. |
| 11/15/2017 | Transfer | firealarm13 | Please correct the following | Please correct the following: | | Remove non operational pull at 3rd floor sky bridge to Nordstroms. |
| 11/15/2017 | Transfer | firealarm11 | Fire Alarm approved CCO | Fire Alarm approved for CCO | | This inspection is for the third floor common area detection and notification. Note to the mall manegement that a CCO for the alarm will not be given until all suite addressing is the same as the fire alarm description. This has been discussed several times with the mall that it will be required. |