Inspection #: 469426
Inspection Type: Electrical Rough
Inspector: M.Green
Result: Partial
Comment: Sales floor drop ceilings electrical rough approved. Also, recessed lights at storefront soffit electrical rough approved. Stock room ceiling to be open. Did not inspect resroom ceiling.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
8/16/2017Corrected01See inspection comments Stock room and Bathroom ceilings incomplete.  
8/16/2017Corrected01See inspection comments Data cables ran above ceiling for use. Properly support cabling.  
8/16/2017Corrected01See inspection comments Various locations. Properly support MC cabling. Support within 12" of junction box. Ceiling seismic wire not permitted as support.  
8/16/2017Corrected01See inspection comments Properly support fire alarm cabling. No support currently installed.  
8/16/2017Corrected01See inspection comments Various locations. Demo unused low volt/Data wiring. Is camera cabling to be used? Must be properly supported.  
8/16/2017Corrected01See inspection comments Electrical support wires must be secured at both ends. 
8/16/2017Corrected01See inspection comments Throughout area. Electrical support wires must be identified. 