Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To View Another Inspection


Inspection #: 468926
Inspection Type: Electrical Rough
Inspector: E.Widman
Result: Correction
Comment: See corrections for server room area at UPS, new panel 4B, and bypass switch.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
9/29/2017Transfer01See inspection comments Feed to bypass switch in server room. #3 cu ran to bypass. Plans call for #2 cu. Equipment and ckts rated 100 amp or less must use conductors referenced in 110.14 (C) (1), and use next higher standard ampere rating. Reference 240.4 (B) and 240.6 (A).
9/29/2017Transfer01See inspection comments Securely fasten flexible conduit at UPS.  
ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter      RSS