| Date | Status | Code | Description | Ref | Location | Comments |
| 9/29/2017 | Transfer | 01 | See inspection comments | | Feed to bypass switch in server room. | #3 cu ran to bypass. Plans call for #2 cu. Equipment and ckts rated 100 amp or less must use conductors referenced in 110.14 (C) (1), and use next higher standard ampere rating. Reference 240.4 (B) and 240.6 (A). |
| 9/29/2017 | Transfer | 01 | See inspection comments | | Securely fasten flexible conduit at UPS. | |