Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To View Another Inspection


Inspection #: 466864
Inspection Type: Electrical Rough
Inspector: E.Widman
Result: Correction
Comment: See corrections. Schedule reinspection.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
8/16/2017Transfer01See inspection comments Stock room and Bathroom ceilings incomplete.  
8/16/2017Transfer01See inspection comments Data cables ran above ceiling for use. Properly support cabling.  
8/16/2017Transfer01See inspection comments Various locations. Properly support MC cabling. Support within 12" of junction box. Ceiling seismic wire not permitted as support.  
8/16/2017Transfer01See inspection comments Properly support fire alarm cabling. No support currently installed.  
8/16/2017Transfer01See inspection comments Various locations. Demo unused low volt/Data wiring. Is camera cabling to be used? Must be properly supported.  
8/16/2017Transfer01See inspection comments Electrical support wires must be secured at both ends. 
8/16/2017Transfer01See inspection comments Throughout area. Electrical support wires must be identified. 
ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter