Inspection #: 465921
Inspection Type: Final Electrical
Inspector: M.Green
Result: Approved
Comment: Items from 7/21/2017 inspection corrected. Electrical final approved. Field evaluation of lighted display cases not required in this case because of the following factors: 1. Low voltage lighting is a "plug and play" system. 2. The low voltage transformers have been found to be listed, class 2 units. The LED tape strip lighting is listed. 3. All external appearaces indicate that the low voltage system meets NEC 411.4(A) or (B).