Date | Status | Code | Description | Ref | Location | Comments |
7/21/2017 | Transfer | 01 | See inspection comments | | Trim missing at bathroom luminaire. | |
7/21/2017 | Transfer | 01 | See inspection comments | | Existing J-box and conduit in electrical room must be properly supported. | |
7/21/2017 | Transfer | 01 | See inspection comments | | Overall listing for lighted showcase shelving. Lighting does not appear to be UL listed, or fed with a class 2 power supply. | |
7/21/2017 | Transfer | 01 | See inspection comments | | Post floor plan lighting plan at panels/ lighting control panel. | |
7/17/2017 | Transfer | 01 | See inspection comments | | 1 em luminaire in east side of area not functioning. | |
7/17/2017 | Transfer | 01 | See inspection comments | | Showcase cabinets do not appear to be listed. Power supplies for luminaires does not appear to be Class 2. | |