Inspection #: 465132
Inspection Type: Fire Sprinkler Final
Inspector: B.Meinhardt
Result: Approved
Comment: Fire sprinkler system for permit F17-1076 is approved for CO...... Clothing is class IVproduct.( worse case). Please reference the attached graph . . The submitted design for the American Eagle store is ordinary gr 2. This design is adequate for racks up to 10 feet with a class IV product. ..This submitted design is adequate for the racks noted in the inspection report. ..NFPA 13 standard reference: ..16.1.3 Movable Racks. .. Rack storage in movable racks shall be protected in the same manner as multiple-row racks. .. 16.2.1.1 .. The area and density for the hydraulically remote area and the water supply shall be determined as specified in 16.2.1.2 for storage up to 12 ft (3.7 m) and 16.2.1.3 to 16.2.1.3.5 for storage over 12 ft (3.7 m). .. 16.2.1.2 Protection Criteria for Rack Storage of Class I Through IV Commodities Stored Up to 12 ft (3.7 m) in Height. .. 16.2.1.2.1 .. The protection criteria for storage up to and including 12 ft (3.7 m) shall be the same as miscellaneous storage, selected from Chapter 13. .. 16.2.1.2.2 The protection criteria in Chapter 13 shall be acceptable for storage of Class I through Class IV commodities up to and including 12 ft (3.7 m) in height. (See Table 13.2.1 for specific Class I through Class IV storage height protection criteria.)

Inspection Corrections