Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To View Another Inspection


Inspection #: 465023
Inspection Type: Electrical Rough
Inspector: E.Widman
Result: Partial
Comment: See corrections. Electrical conditionally approved for move in only. Complete electrical final pending corrections.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
7/21/2017Transfer01See inspection comments Trim missing at bathroom luminaire.  
7/21/2017Transfer01See inspection comments Existing J-box and conduit in electrical room must be properly supported.  
7/21/2017Transfer01See inspection comments Overall listing for lighted showcase shelving. Lighting does not appear to be UL listed, or fed with a class 2 power supply.  
7/21/2017Transfer01See inspection comments Post floor plan lighting plan at panels/ lighting control panel. 
7/19/2017Corrected01See inspection comments Open j box under center check out.  
7/19/2017Corrected01See inspection comments Exit light in west fitting not functioning properly.  
7/19/2017Corrected01See inspection comments Luminaires not permitted to be supported by wall board. Center light. 
7/19/2017Corrected01See inspection comments Open j-box above center luminaire on west side.  
7/19/2017Corrected01See inspection comments fitting room lights do not appear to be UL listed.  
7/17/2017Transfer01See inspection comments 1 em luminaire in east side of area not functioning.  
7/17/2017Corrected01See inspection comments More than 3 lighting ckts for unbroken area, and originating in same panelboard. Lock on feature req'd for EM ckts.  
7/17/2017Transfer01See inspection comments Showcase cabinets do not appear to be listed. Power supplies for luminaires does not appear to be Class 2.  
ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter