Inspection #: 463700
Inspection Type: Electrical Rough
Inspector: M.Green
Result: Correction
Comment: Some items corrected others remain uncorrected. Can call inspector, Mike Green at 317-6980

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
6/30/2017Corrected01See inspection comments Under mobile home.Support, fasten MC cable off of ground to trailer frame.
6/30/2017Transfer01See inspection comments Exterior receptacles including any receptacles under trailer for water line heat tape, etc.Verify GFCI protection. If replacing receptacle(s) will need to be weather resistant and tamper resistant type with "extra duty" weatherproof cover.
6/30/2017Transfer01See inspection comments Headbolt heater receptacle.Receptacle needed by parking area for plugging-in car engine block heaters. Needs dedicated circuit. Needs "extra-duty" weatherproof cover. Needs GFCI protection. Receptacle will need to be tamper resistant and weather resistant type.
6/30/2017Corrected01See inspection comments Jacuzzi tub.Needs GFCI breakers for motor and heater. Needs 16 inch by 16 inch access panel. Receptacles need to face access.
6/30/2017Corrected01See inspection comments Kitchen conuntertop.Receptacles need GFCI protection.
6/30/2017Transfer01See inspection comments Panel.Will need panel schedule by final
6/30/2017Transfer01See inspection comments Feeder J-box under mobile home.Needs ground wire connections. Do not feed GEC to ground rod through metal conduit and meta box without bonding to the metal box and both ends of the metal raceway.
6/30/2017Corrected01See inspection comments Water line and gas line under trailer.Needs #6 copper grounding electrode conductor from panel. Do not run through metal conduit. Cannot be spliced.
6/30/2017Transfer01See inspection comments 3-wire feeder from service.Mobile home is more than 30 feet from service. Needs post mounted disconnect at the trailer space. Also requires the following: *Treated wood for post. *Disconnect needs to be labelled "suitable for use as service equipment". *(2) ground rods needed at post mounted disconnect. *Connect ground rods to disconnect with #6 copper wire. *Bond neutral to ground at disconnect. *Feeder from post mounted disconnect into mobile home needs to include a #6 copper ground wire. *Feeder underground from post mounted disconnect to trailer will need to be burried 24 inches deep and inspected before cover. *Coreflow will need to cover feeders completely where above ground under mobile home.