| Date | Status | Code | Description | Ref | Location | Comments |
| 7/11/2017 | Transfer | Correct Below | * | | Disconnect req'd for seperate structure. Reference 225.32. | |
| 7/11/2017 | Transfer | Correct Below | * | | Label disconnect @ panel. | |
| 7/11/2017 | Transfer | Correct Below | * | | Provide installation instructions at next inspection for review. What is max OCP? #14 cu conductors used in controller to feed unit. 20 amp breaker installed. | |
| 7/11/2017 | Transfer | Correct Below | * | | Ko seal req'd at bottom of external j-box at gate opener. | |