Inspection #: 462809
Inspection Type: Final Electrical
Inspector: E.Widman
Result: Correction
Comment: See corrections.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
7/11/2017TransferCorrect Below* Disconnect req'd for seperate structure. Reference 225.32.  
7/11/2017TransferCorrect Below* Label disconnect @ panel.  
7/11/2017TransferCorrect Below* Provide installation instructions at next inspection for review. What is max OCP? #14 cu conductors used in controller to feed unit. 20 amp breaker installed.  
7/11/2017TransferCorrect Below* Ko seal req'd at bottom of external j-box at gate opener.  