Inspection #: 462136
Inspection Type: Electrical Rough
Inspector: E.Widman
Result: Correction
Comment: See corrections. Inspection is for main area only. Stock room, electric room, and fitting not inspected on this trip. Partially incomplete.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
7/17/2017Transfer01See inspection comments 1 em luminaire in east side of area not functioning.  
7/17/2017Transfer01See inspection comments More than 3 lighting ckts for unbroken area, and originating in same panelboard. Lock on feature req'd for EM ckts.  
7/17/2017Transfer01See inspection comments Isolated ground receptacles not functioning properly.  
7/17/2017Transfer01See inspection comments Showcase cabinets do not appear to be listed. Power supplies for luminaires does not appear to be Class 2.  
7/17/2017Transfer01See inspection comments Provide UL listing information and installation instructions.  