Date | Status | Code | Description | Ref | Location | Comments |
7/17/2017 | Transfer | 01 | See inspection comments | | 1 em luminaire in east side of area not functioning. | |
7/17/2017 | Transfer | 01 | See inspection comments | | More than 3 lighting ckts for unbroken area, and originating in same panelboard. Lock on feature req'd for EM ckts. | |
7/17/2017 | Transfer | 01 | See inspection comments | | Isolated ground receptacles not functioning properly. | |
7/17/2017 | Transfer | 01 | See inspection comments | | Showcase cabinets do not appear to be listed. Power supplies for luminaires does not appear to be Class 2. | |
7/17/2017 | Transfer | 01 | See inspection comments | | Provide UL listing information and installation instructions. | |