| Date | Status | Code | Description | Ref | Location | Comments |
| 7/27/2017 | | firealarm6 | FACP map | Floor plan/map required at main entry door showing location of FACP. | | Provide Zone Map at fire alarm panel for Daycare area with decription from panel programming |
| 7/27/2017 | | firealarm13 | Please correct the following | Please correct the following: | | 1. Missing horn strboe in reception 100 2. Bathroom 105 horn strobe not working. 3. Missing smoke in Gym. |
| 7/27/2017 | | firealarm13 | Please correct the following | Please correct the following: | | strobe candela setting are incorrect for room size, addjust per NFPA 72 requirements |
| 7/27/2017 | | firealarm1 | Provide plans | Provide approved plans on site for inspection. | | plans on site were superceeded, go to MOA permit center and get approved plans |
| 7/27/2017 | | firealarm13 | Please correct the following | Please correct the following: | | Remove bells in hallway where new horn strobes are installed |
| 7/27/2017 | | firealarm11 | Fire Alarm approved CCO | Fire Alarm approved for CCO | | Fire Alarm approved for CCO till August 30, 2017 |