Inspection #: 460363
Inspection Type: Final Electrical
Inspector: E.Widman
Result: Correction
Comment: See corrections.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
10/12/2017 Correct Below* Update address of project. Building labeling does not match permit. 
10/12/2017TransferCorrect Below* How is secondary overcurrent protection at individual transformers for unit heaters provided?  
10/12/2017TransferCorrect Below* Update panel schedule.  
10/12/2017TransferCorrect Below* Space heating is Continuous load. Reference 424.3 (B). Provide load calculation for connected load for Unit heater ckt. (Building 4055). 