Inspection #: 456454
Inspection Type: Electrical Rough
Inspector: M.Green
Result: Correction
Comment: Dave and Buster's core and shell: stairs to main entrance. New electrical work is approved. Corrections items are existing conditions.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
8/7/2017Corrected01See inspection comments Stair way.There is an existing 2 inch conduit that appears to enter an air duct and run longitudinally. 300.22 does not allow conduits in ducts unless for duct work actuation or sensing.
8/7/2017Corrected01See inspection comments Stairway ceiling.Stair may or may not be of a classification that does not allow circuits for other loads to pass through. Need to verify stair type with structural.