Inspection #: 456450
Inspection Type: Electrical Rough
Inspector: M.Green
Result: Correction
Comment: Pre- inspection for 1600A service to feed Dave and Buster's. 110.26(E)(2)(b) normally requires dedicated space to a height of 6 feet above the equipment. Electrical conduits foreign to this installation pass above the equipment. the dedicated space requirement is waived per NEC 90.4. The conduits in question only pass over a small portion of the utility side of the underground fed service switchboard.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
8/9/2017Transfer01See inspection comments Service grounding electrode system.Will need to confirm connection to water line.
8/9/2017Transfer01See inspection comments Service latteral conduits.#4/0 CU is too small to bond (4) parallel runs for a 1600A service. (1) 4/0 CU can be used to bond (2) parallel rums,