Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To View Another Inspection


Inspection #: 456221
Inspection Type: Electrical Rough
Inspector:
Result:
Comment:

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
5/24/2017 01See inspection comments Low volt wiring req'd to be supported in area. Much of which appears to be going through to next unit.  
5/24/2017 01See inspection comments Access req'd to water connection for seperately derived system.  
5/24/2017 01See inspection comments Equipment ground req'd for xfmr to enclosure.  
5/24/2017 01See inspection comments Support for MC cable near store front.  
5/24/2017 01See inspection comments Seismic support and attach luminaire to grid at right rear of area.  
5/24/2017 01See inspection comments Open jbox at rear of area.  
5/24/2017 01See inspection comments Remove temp lighting from above accessible ceiling.  
ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter