Inspection #: 455552
Inspection Type: Electrical Rough
Inspector: E.Widman
Result: Correction
Comment: See corrections.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
5/24/2017Transfer01See inspection comments Low volt wiring req'd to be supported in area. Much of which appears to be going through to next unit.  
5/24/2017Transfer01See inspection comments Access req'd to water connection for seperately derived system.  
5/24/2017Transfer01See inspection comments Equipment ground req'd for xfmr to enclosure.  
5/24/2017Transfer01See inspection comments Support for MC cable near store front.  
5/24/2017Transfer01See inspection comments Seismic support and attach luminaire to grid at right rear of area.  
5/24/2017Transfer01See inspection comments Open jbox at rear of area.  
5/24/2017Transfer01See inspection comments Remove temp lighting from above accessible ceiling.  