Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To View Another Inspection


Inspection #: 453174
Inspection Type: Framing / Ext.
Inspector: B.Gilgus
Result: Correction
Comment: Requested by: jerry michel 244-8089 jmichel_asds@yahoo.com

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
5/9/2017TransferEXTFRAMECSee Inspector commentsInspector commentsrestroom 101/ stockroom 102 1**floor penatration for closet flange penatrating 2 hour floor /ceiling assembly requires protection of thru penatration 2hr with F&T rating including fire caulking all thru floor penatrations inside wall cavitys. wall framing connections at pandeck above will need to repair mono kote to be repaired. metal framing to be approved after corrections of fire separation. recall
ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter