Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To View Another Inspection


Inspection #: 451068
Inspection Type: Electrical Rough
Inspector: M.Green
Result: Partial
Comment: Combined Aerie / American Eagle tennant space. Electrical wall rough approved except: North end of east exterior wall. American Eagle / stock room common wall. American Eagle hall to changing rooms. NOTES: 1.Gutter above panels. Conductor fill in gutters must comply with 366.22(A) and 366.23(A). 2. Panels are in (1) stock room. OCPDs need to be readily accessible to both tennants in this TI space per 240.19(B).

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
       
ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter