Inspection #: 450498
Inspection Type: Final Electrical
Inspector: O.Burbridge
Result: Correction
Comment: electrical final for gamma knife approved

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
4/18/2017CorrectedCorrect Below* provide stamped approved drawings 
4/18/2017TransferCorrect Below* working clearance required for panel B 
4/18/2017CorrectedCorrect Below* in x-ray room back room - show electrical ratings in Brainlab cabinet on left wall 
4/18/2017CorrectedCorrect Below* at hallway cabinet - working clearances required at 30 amp surge breaker - no apparent third party listing on cabinet or internal UPS 