Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To View Another Inspection


Inspection #: 450340
Inspection Type: Final Electrical
Inspector: D.Rooney
Result: Correction
Comment: Corrections - only inspected Lineak area

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
4/18/2017TransferCorrect Below* provide stamped approved drawings 
4/18/2017TransferCorrect Below* working clearance required for panel B 
4/18/2017TransferCorrect Below* in x-ray room back room - show electrical ratings in Brainlab cabinet on left wall 
4/18/2017TransferCorrect Below* at hallway cabinet - working clearances required at 30 amp surge breaker - no apparent third party listing on cabinet or internal UPS 
ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter      RSS