Inspection #: 450192
Inspection Type: Fire Sprinkler Final
Inspector: B.Meinhardt
Result: Partial
Comment: Fire Sprinkler Final, 90-Devices, Contact is Billy Bayer 229-5571 Requested by: Wendee Gilchrist 907-336-5000 wgilchrist@gmwfire.com

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
7/19/2017 firesprinklr14Correction(s) #1<div>Correct the following item(s):</div><div><br></div> high density rolling storage racks for clothing were not shown on the plans. Provide hydraulic cals and code requirements for this type of storage. largest rack is 10'2" high x 10' deep x 21' long. 3 total areas with this type of racking
7/19/2017 firesprinkl13CCO ApprovedCCO approved for fire sprinkler system CCO approved till 1 september 2017